R.I. Gen. Laws § 23-27.3-101.5

§ 23-27.3-101.5. SAFE Units — Requirements.

SAFE Units, as defined in § 45-24-31, that are provided as a permitted use pursuant to § 45-24-37, or as part of a municipality’s exercise of limited emergency authority pursuant to § 45-24-78, shall be allowed under this code; provided that, the unit:

(1) Is confirmed by the state fire marshal, where applicable, or local fire marshal, and a state building official, to comply with the following:

(i) Standard requirements to qualify as a SAFE Unit shall include:

(A) Climate control;

(B) A locking door;

(C) Hardwired smoke detectors or sealed battery-operated smoke alarm(s) and hardwired carbon monoxide detectors or sealed battery-operated carbon monoxide alarm(s), as such terms are defined by the National Fire Protection Association (“NFPA”) 72;

(D) A two- and one-half pound (2.5 lb.) ABC fire extinguisher;

(E) An egress window or secondary emergency egress door;

(F) The unit meets at least class C fire rating of the International Building Code; and

(2) Size requirement. Each unit shall have an interior floor area of not less than seventy square feet (70 sq. ft.) for one occupant; when more than one person occupies the unit, the required floor area shall be increased at the rate of fifty square feet (50 sq. ft.) for each occupant in excess of one; and the total interior floor area shall not exceed four hundred square feet (400 sq. ft.); and

(3) Live loads requirement. SAFE Units shall be designed to resist intrusion of wind, rain, and snow and to support the following live loads:

(i) Floor live loads of not less than forty pounds (40 lbs.) per square foot of floor area;

(ii) Horizontal live loads of not less than fifteen pounds (15 lbs.) per square foot of vertical wall and roof area;

(iii) Roof live loads of not less than twenty pounds (20 lbs.) per square foot of horizontal roof area;

(iv) In areas where snow loads are greater than twenty pounds (20 lbs.) per square foot, the roof shall be designed and constructed to resist these additional loads;

(v) The units shall have adequate anchorage to address these loads; and

(4) Ceiling height requirement. Habitable space shall have a ceiling height of not less than eighty inches (80″) and obstructions shall not extend below these minimum ceiling heights; and

(5) Egress window requirement. The egress window shall:

(i) Not be more than forty-four inches (44″) above the floor;

(ii) Have a minimum net clear opening height of twenty-four inches (24″);

(iii) Have a minimum net clear opening width of twenty inches (20″); and

(iv) Have a minimum net clear opening area of five square feet (5 sq. ft.); and

(6) Plumbing and gas service requirement. If a SAFE Unit contains plumbing or gas service it shall comply with all applicable requirements of the building and fire codes for plumbing and gas service; and

(7) Electrical requirement. SAFE Units shall be provided with all of the following installed in compliance with the applicable provisions of the electrical code:

(i) A continuous source of electricity, except that the source may be an emergency generator or renewable source of power;

(ii) A minimum of one interior light fixture with a battery backup;

(iii) Electrical heating equipment listed for residential use and a dedicated receptacle outlet for the electrical heating equipment, unless a nonelectrical source of heating is provided; and

(iv) At least one GFCI-protected receptacle outlet for use by the occupant(s); and

(8) Ventilation requirement. SAFE Units shall be provided with means of ventilation (natural or mechanical) allowing for air replacement; and

(9) Accessory units such as bathrooms shall comply with the construction requirements for a SAFE Unit or shall be considered a self-contained facility; and

(10) Separation requirement. The SAFE Unit, when part of a community of SAFE Units, has a minimum separation between other SAFE Units of greater than ten feet (10′).

History of Section.
P.L. 2026, ch. 327, § 2, effective June 23, 2026; P.L. 2026, ch. 328, § 2, effective June 23, 2026.